OT302
The ORENA OT302 is a 2-wire, non-polarity conventional photoelectric smoke detector operating at 24VDC, featuring a high-sensitivity optical chamber for detecting smoldering fires with low false alarm rates.
Designed without base for flexible mounting options, it connects directly to conventional fire panels and uses advanced light-scattering technology with insect-resistant mesh for reliable performance in various environments.
| Specification | Details |
|---|---|
| Part Number | OT302 |
| Type | 2-wire photoelectric smoke, non-polarity |
| Operating Voltage | DC 12-28V (nominal 24VDC) |
| Quiescent Current | ≤60 µA |
| Alarm Current | ≤20 mA @24VDC w/1kΩ resistor |
| Coverage Area | 60 m² |
| Dimensions | Ø100 × 51 mm (w/base); 45 mm (head only) |
| Weight | 70g (head only); 142g (w/base) |
| Operating Temp | -10°C to +50°C |
| Humidity | ≤95% RH (non-condensing) |
| Standards | EN54-7 |