714/001/115
The Honeywell 714/001/115 is the full single-loop DXc Series fire alarm control panel (unlike the half-loop 714/001/105), supporting up to 198 addressable devices across Morley, Apollo, Hochiki, and System Sensor protocols with multi-protocol flexibility.
It includes 2 monitored sounder circuits, 80 logical zones (expandable to 160 LEDs), backlit 6x40 LCD display, full control keys (Evacuate, Silence/Resound, Reset), USB programming, and 500 event log.Key Specifications
| Feature | Details |
|---|---|
| Loop Capacity | 1 loop (99 detectors + 99 modules = 198 devices total) |
| Sounder Circuits | 2 x 0.5A monitored @24VDC |
| Display | 6x40 backlit LCD (240x64 pixels), 80/160 zone LEDs optional |
| Power Supply | 230VAC mains; 2 x 12Ah batteries (72hr standby) |
| Dimensions | 260 x 390 x 147mm (H x W x D); 4kg |
| Relays | Fire, Fault (1A@30VDC each) |
| Temperature | 0°C to +40°C; IP30 |