MI/DCZRME
The Honeywell MI/DCZRME is an addressable conventional zone interface/monitor module that connects legacy non-addressable detectors or call points to Morley-IAS intelligent fire alarm loops, providing one supervised zone input with remote reset capability and external fault monitoring.
It includes a built-in short-circuit isolator (EN54-17 compliant), supports up to 25 conventional devices per zone with 3.9kΩ EOL resistor, and features tri-color LED status plus DIN rail mounting option.Key Specifications
| Feature | Details |
|---|---|
| Zone Capacity | Up to 25 conventional detectors/MCPs; 3.9kΩ EOL |
| Voltage | 18-28.5 VDC loop-powered |
| Quiescent Current | 375 µA @24V |
| Dimensions | 23 x 93 x 83 mm (H x W x D); 110g |
| Temperature | -20°C to +60°C |
| Humidity | 5-95% RH non-condensing |
| Terminals | Max 2.5mm² wire gauge |
| Standards | EN54-17, EN54-18; LPCB approved |