X-DCS2000
The Honeywell X-DCS2000 is the core unit of the X-618 Public Address and Voice Alarm System, integrating zone expansion, audio source management, network audio, broadcasting, zone control, monitoring, and fault diagnosis through its powerful audio matrix structure.
It supports 8 loudspeaker circuit outputs with fault detection (500W max, 250W supervised), 4 auxiliary inputs for external sources, 4 noise-activated microphone inputs with phantom power, and automatic operation/fault logging up to 10,000 events each.Key Specifications
| Feature | Details |
|---|---|
| Power Supply | 100-240VAC/50-60Hz main; DC 21.5-28.5V backup; 120W max |
| Audio Outputs | 8 zones (500W max, 250W supervised); 4 audio outputs (1.2V) |
| Audio Inputs | 4 aux (1V), 4 AVC mics (14mV/330mV selectable) |
| Frequency Response | 60Hz-16kHz; SNR >85dB (aux), >65dB (AVC) |
| Networking | 4x 10/100M Ethernet ports; 1GB storage |
| Trigger I/O | 8 inputs, 8 relay outputs (2.5A @ AC250V/DC30V) |
| Dimensions | 482 x 88 x 420mm (1U rack); Operating: -10°C to +55°C |