The Edwards 3-CPU3 is the central processing unit module for EST3 fire alarm and life safety systems, serving as the master controller for chassis-mounted rail modules.
It automatically learns module configurations on power-up, handles inter-module communications via broadcast protocol, and provides network connectivity for multi-node systems up to 64 nodes.

Key Specifications

FeatureSpecification
MountingFirst two slots of 3-CHAS7 rail chassis ​
Voltage24 VDC ​
Current145 mA standby / 155 mA alarm ​
Relays3 × Form-C (30 VDC @ 1 A): alarm, supervisory, trouble ​
CommunicationRS-485 (network), RS-232 (maintenance) ​
MemoryNon-volatile, 1,000 history events ​
FeaturesAuto module learning, firmware upgrades, ground fault detection, watchdog supervision ​
Temp/Humidity32°F-120°F (0°C-49°C); 93% RH non-condensing 